Transformers

Transformer formulas, delta-wye connections, full-load currents, and OCPD sizing.

6 reference items · 3 sections

Transformer Formulas

Turns Ratio

V_p / V_s = N_p / N_s = I_s / I_p
Transformer Turns Ratio
VariableDescriptionUnit
V_pPrimary voltageVolts
V_sSecondary voltageVolts
N_pPrimary turnscount
N_sSecondary turnscount
I_pPrimary currentAmperes
I_sSecondary currentAmperes
Variations:Find V_s: V_s = V_p × (N_s / N_p)Find I_p: I_p = I_s × (V_s / V_p)
Voltage ratio equals turns ratio. Current ratio is inverse of voltage ratio (power in = power out for ideal transformer).

Transformer Current from kVA

NEC 450.3
I = (kVA × 1000) ÷ V
Single-Phase Transformer Current
VariableDescriptionUnit
IFull-load currentAmperes
kVATransformer ratingkVA
VVoltage (primary or secondary)Volts
I = (kVA × 1000) ÷ (V × 1.732)
Three-Phase Transformer Current
VariableDescriptionUnit
IFull-load currentAmperes
kVATransformer ratingkVA
VLine voltageVolts

Quick Reference: Common Transformer Currents

Transformer Full-Load Currents
kVA120V 1Φ240V 1Φ208V 3Φ480V 3Φ
32512.58.33.6
54220.813.96.0
108341.727.812.0
1512562.541.618.0
2520810469.430.1
37.531315610445.1
4537518812554.1
5041720813960.1
7562531320890.2
100833417278120
1501250625416180
2001667833555240
30025001250833361
500416720831388601

1.Values rounded to nearest whole amp for large values

2.Use these for sizing OCPD and conductors

Transformer Connections

Delta-Wye Connection

Most common three-phase distribution transformer connection.

Delta (Δ) Primary

• Line voltage = Phase voltage • Line current = Phase current × √3 • No neutral on primary side • Provides isolation from primary ground faults

Wye (Y) Secondary

• Line voltage = Phase voltage × √3 • Line current = Phase current • Neutral point available • Common: 208Y/120V, 480Y/277V

Voltage Relationships

Common Delta-Wye Configurations
Primary (Delta)Secondary (Wye)Phase-Neutral
480V208Y/120V120V
480V480Y/277V277V
4160V480Y/277V277V
12,470V208Y/120V120V

Wye-Wye Connection

Both primary and secondary in wye (star) configuration. • Both sides have neutral available • Requires careful attention to harmonic currents • Must handle zero-sequence currents • Less common than delta-wye • Used when neutral is needed on both primary and secondary

Delta-Delta Connection

Both primary and secondary in delta configuration. • No neutral on either side • Can operate as open-delta if one transformer fails (at ~57.7% capacity) • Good for industrial loads without neutral requirement • Line voltage = Phase voltage on both sides

Transformer OCPD Sizing

Transformer Overcurrent Protection

Maximum OCPD for Transformers >600V
LocationProtection MethodMax % of Rated Current
Primary onlyFuse300%
Primary onlyCircuit breaker300%
Primary + SecondaryPrimary fuse250%
Primary + SecondarySecondary fuse250%

Transformers 600V and Below

Maximum OCPD for Transformers ≤600V (NEC 450.3(B))
ConditionPrimary MaxSecondary Max
Primary only protection125%*N/A
Pri ≥9A + Sec ≥9A250%125%*
Pri ≥9A + Sec <9A250%167%
Pri <9A + Sec ≥9A167%125%*
Pri <9A + Sec <9A167%167%

1.* If 125% does not correspond to standard size, next higher standard size permitted

2.Primary current = kVA × 1000 ÷ V_primary (single-phase)

3.Primary current = kVA × 1000 ÷ (V_primary × 1.732) (three-phase)

4.Where primary OCPD meets requirements, secondary protection is not required for 2-wire transformer secondaries

Take It With You

Access quick reference, 8,000+ practice questions, and NEC calculators anywhere with the NEC Mastery app.