Motor Data

Full-load current tables, branch circuit sizing, OCPD sizing, and NEMA starter sizes.

6 reference items · 4 sections

Single-Phase Motor FLC

Single-Phase AC Motor Full-Load Current

Single-Phase Motor FLC (Amperes)
HP115V200V208V230V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.14.03.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88.0
2011.511.010
22413.813.212
33419.618.717
55632.230.828
8046.044.040
1010057.555.050

1.Use these values (not motor nameplate) for sizing branch circuit components

2.For motor starting, multiply FLC by 6-8× for locked rotor current estimate

Per NEC 430.6(A)(1): Branch circuit conductors, short-circuit protection, and ampacity must be based on FLC from these tables, NOT motor nameplate current.

Three-Phase Motor FLC

Three-Phase AC Motor Full-Load Current

NEC 430.250
Three-Phase Motor FLC (Amperes)
HP208V230V460V575V
½2.42.21.10.9
¾3.53.21.61.3
14.64.22.11.7
6.66.03.02.4
27.56.83.42.7
310.69.64.83.9
516.715.27.66.1
24.222119.0
1030.8281411
1546.2422117
2059.4542722
2574.8683427
3088804032
401141045241
501431306552
601691547762
752111929677
10027324812499
125343312156125
150396360180144
200528480240192

1.Values from NEC Table 430.250

2.For 200V: multiply 208V values by 1.0 (use 208V column)

3.For dual-voltage motors, use the voltage at which motor is connected

Motor Branch Circuit Sizing

Motor Circuit Conductor Sizing

NEC 430.22
Min Ampacity = FLC × 125%
Motor Branch Circuit Conductor
VariableDescriptionUnit
FLCFull-load current from tableAmperes
125%Safety factor for continuous dutymultiplier
Conductor must have ampacity ≥ 125% of motor FLC. Use 75°C column of ampacity table for termination sizing.
Example: 10 HP, 3Φ, 230V motor → FLC = 28A → Min conductor ampacity = 28 × 1.25 = 35A → Use 10 AWG copper (75°C = 35A)

Motor Overcurrent Protection (OCPD) Sizing

NEC 430.52
Maximum OCPD Size (% of Motor FLC)
Protection TypeMax % of FLC
Non-time delay fuse300%
Dual-element (time-delay) fuse175%
Instantaneous trip breaker800%
Inverse time breaker250%

1.If calculated value doesn't match standard size, round UP to next standard size

2.Exception: If next standard size still causes nuisance tripping, may increase per 430.52(C)(1)(b)

Standard Breaker/Fuse Sizes

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A
Example: 10 HP, 3Φ, 230V with inverse time breaker → FLC = 28A → 28 × 2.50 = 70A → Use 70A breaker

Motor Overload Protection

NEC 430.32
Motor Overload Protection Sizing
Motor Service FactorMax Overload %
SF ≥ 1.15125% of nameplate FLA
SF < 1.15115% of nameplate FLA
Temperature rise ≤ 40°C125% of nameplate FLA
Temperature rise > 40°C115% of nameplate FLA

1.Overload protection uses NAMEPLATE current (not table FLC)

2.This is different from branch circuit protection which uses table FLC

Important distinction: Overload protection is sized from the motor NAMEPLATE amps. Branch circuit OCPD and conductors are sized from TABLE FLC values.

Motor Starter (Controller) Sizing

NEMA Motor Starter Sizes

NEC 430.83
NEMA Motor Starter Sizes
NEMA SizeMax HP (1Φ 230V)Max HP (3Φ 230V)Max HP (3Φ 460V)Max Amps
00129
023518
131027
2152545
3305090
450100135
5100200270
6200400540
7300600810

1.NEMA starters sized by HP and voltage

2.— = not applicable for this voltage/phase combination