Grounding & Bonding

EGC and GEC sizing tables, grounding electrode types, and requirements.

3 reference items · 3 sections

Equipment Grounding Conductors (EGC)

Minimum EGC Size by OCPD Rating

Equipment Grounding Conductor Sizing
OCPD Rating (A)Copper EGCAluminum EGC
1514 AWG12 AWG
2012 AWG10 AWG
3010 AWG8 AWG
4010 AWG8 AWG
6010 AWG8 AWG
1008 AWG6 AWG
2006 AWG4 AWG
3004 AWG2 AWG
4003 AWG1 AWG
5002 AWG1/0 AWG
6001 AWG2/0 AWG
8001/0 AWG3/0 AWG
10002/0 AWG4/0 AWG
12003/0 AWG250 kcmil
16004/0 AWG350 kcmil
2000250 kcmil400 kcmil
2500350 kcmil600 kcmil
3000400 kcmil600 kcmil
4000500 kcmil750 kcmil
5000700 kcmil1200 kcmil
6000800 kcmil1200 kcmil

1.EGC must not be smaller than values shown

2.Size based on rating of overcurrent device ahead of equipment

3.Where circuit conductors are increased in size for voltage drop, EGC must be proportionally increased

The EGC provides a low-impedance path for fault current to trip the OCPD. It does NOT carry current during normal operation.

Grounding Electrode Conductors (GEC)

GEC Sizing Based on Service Conductor

NEC 250.66
Grounding Electrode Conductor Sizing
Service Conductor (Cu)Service Conductor (Al)GEC CopperGEC Aluminum
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 AWG or 1/0 AWG2/0 AWG or 3/0 AWG6 AWG4 AWG
2/0 AWG or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 thru 350 kcmilOver 250 thru 500 kcmil2 AWG1/0 AWG
Over 350 thru 600 kcmilOver 500 thru 900 kcmil1/0 AWG3/0 AWG
Over 600 thru 1100 kcmilOver 900 thru 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG250 kcmil

1.GEC connects the service equipment grounding bus to the grounding electrode system

2.For parallel service conductors, use the equivalent area of a single conductor

The GEC to a ground rod or pipe electrode need not be larger than 6 AWG copper or 4 AWG aluminum. The GEC to a concrete-encased electrode (Ufer ground) need not be larger than 4 AWG copper.

Grounding Electrode System

Grounding Electrode Types

NEC 250.52
Grounding Electrode Types & Requirements
Electrode TypeNEC SectionRequirement
Metal water pipe250.52(A)(1)≥10 ft in contact with earth; must be supplemented
Metal building frame250.52(A)(2)Effectively grounded
Concrete-encased (Ufer)250.52(A)(3)≥20 ft of ½" rebar or 4 AWG bare Cu in footing
Ground ring250.52(A)(4)≥20 ft of 2 AWG bare Cu, ≥30" deep
Ground rod/pipe250.52(A)(5)≥8 ft long, ≥⅝" diameter (rod)
Other listed electrodes250.52(A)(6)Per manufacturer listing
Plate electrode250.52(A)(7)≥2 sq ft exposed to soil, ≥30" deep

1.If available, metal water pipe and building frame MUST be used

2.Single ground rod must achieve ≤25Ω; if not, install a second rod

A supplemental electrode is required when using a metal water pipe electrode. Two ground rods spaced ≥6 ft apart are accepted without resistance testing per 250.53(A)(2).