Wire Properties

AWG conductor physical properties, resistance values, and insulation type ratings.

3 reference items · 2 sections

AWG Conductor Properties

Copper Conductor Properties

NEC Chapter 9, Table 8
Copper Conductor Physical Properties
AWG/kcmilArea (cmil)Diameter (in)Ω/1000ft @75°CWeight lb/1000ft
181,6200.04037.774.92
162,5800.05084.897.81
144,1100.06413.0712.4
126,5300.08081.9319.8
1010,3800.10191.2131.4
816,5100.12850.76450.0
626,2400.1620.49179.4
441,7400.2040.308126
352,6200.2290.245159
266,3600.2580.194200
183,6900.2890.154253
1/0105,6000.3250.122319
2/0133,1000.3650.0967402
3/0167,8000.4100.0766507
4/0211,6000.4600.0608639
250250,0000.5000.0515756
300300,0000.5480.0429907
350350,0000.5920.03671,058
400400,0000.6320.03211,209
500500,0000.7070.02581,511
600600,0000.7750.02141,814
750750,0000.8660.01712,267
10001,000,0001.0000.01293,023

1.DC resistance at 75°C for stranded, uncoated copper conductors

2.Solid conductor resistance is slightly lower (e.g., 14 AWG solid ≈ 3.14 Ω/1000ft)

3.Circular mil (cmil) = diameter in mils squared

4.1 kcmil = 1,000 circular mils

Aluminum Conductor Properties

NEC Chapter 9, Table 8
Aluminum Conductor Physical Properties
AWG/kcmilArea (cmil)Ω/1000ft @75°CWeight lb/1000ft
126,5303.186.03
1010,3802.009.58
816,5101.2615.2
626,2400.80824.2
441,7400.50838.4
352,6200.40348.4
266,3600.31961.0
183,6900.25377.0
1/0105,6000.20197.0
2/0133,1000.159122
3/0167,8000.126154
4/0211,6000.100194
250250,0000.0847230
300300,0000.0707276
350350,0000.0605322
400400,0000.0529368
500500,0000.0424460
750750,0000.0282690
10001,000,0000.0212921

1.DC resistance at 75°C for stranded conductors

2.Aluminum is approximately 61% the conductivity of copper

3.Aluminum conductor is roughly 1/3 the weight of copper for same size

Conductor Insulation Types

Conductor Insulation Types & Temperature Ratings

NEC 310.104(A)
Conductor Insulation Types (NEC Table 310.104(A))
TypeTemp RatingApplicationOuter Covering
TW60°CDry & wet locationsNone
THW75°CDry & wet locationsNone
THWN75°CDry & wet locationsNylon jacket
RHW75°CDry & wet locationsMoisture-resistant
XHHW75°C wet/90°C dryDry & wet locationsNone
THHN90°C dry onlyDry locations onlyNylon jacket
THWN-290°C dry & wetDry & wet locationsNylon jacket
XHHW-290°C dry & wetDry & wet locationsNone
RHH90°C dry onlyDry locations onlyMoisture-resistant
USE75°CUnderground service entranceMoisture-resistant
USE-290°CUnderground service entranceMoisture-resistant

1.THHN/THWN-2 is the most commonly used building wire

2.90°C ampacity can be used for derating, but final ampacity limited to termination temp (usually 75°C)

3.Wet locations: conduit below grade, exterior, or areas subject to saturation

Common Cable/Wiring Methods

Cable & Wiring Method Temperature Ratings
TypeConductor TempDescription
NM-B90°C*Non-metallic sheath (Romex) — dry locations
UF-B90°C*Underground feeder — direct burial rated
MCPer conductorMetal-clad cable — various locations
ACPer conductorArmored cable (BX) — dry locations
MI250°CMineral insulated — special/hazardous applications

1.* NM-B and UF-B conductors are rated 90°C, but ampacity is limited to the 60°C column per NEC 334.80 and 340.80

2.Cable types are wiring methods (NEC Articles 320-340), not insulation designations