Voltage Drop

Single-phase and three-phase voltage drop formulas, lookup tables, and max distance charts.

5 reference items · 4 sections

Voltage Drop Formulas

Single-Phase Voltage Drop

VD = (2 × K × I × D) ÷ CM
Single-Phase Voltage Drop
VariableDescriptionUnit
VDVoltage dropVolts
KResistivity constant12.9 (Cu) / 21.2 (Al)
ILoad currentAmperes
DOne-way distanceFeet
CMWire areaCircular mils
Variations:Find CM: CM = (2×K×I×D) ÷ VD% VD: %VD = (VD ÷ V_source) × 100
K = 12.9 for copper at 75°C. K = 21.2 for aluminum at 75°C. The factor of 2 accounts for the round-trip distance.

Three-Phase Voltage Drop

VD = (1.732 × K × I × D) ÷ CM
Three-Phase Voltage Drop
VariableDescriptionUnit
VDVoltage dropVolts
1.732√3
KResistivity constant12.9 (Cu) / 21.2 (Al)
ILine currentAmperes
DOne-way distanceFeet
CMWire areaCircular mils
Variations:Find CM: CM = (1.732×K×I×D) ÷ VD
Uses 1.732 instead of 2 for three-phase circuits.

Single-Phase Voltage Drop Tables

Voltage Drop — 120V Copper (per 100 ft, per amp)

NEC 210.19(A) Info Note 4
Voltage Drop per Amp per 100 ft — 120V 1Φ Copper
AWGVD/A/100ftMax Amps @3%Max Amps @5%
140.635.79.5
120.409.015.0
100.2514.424.0
80.1622.537.5
60.1036.060.0
40.0660.0100.0
20.0490.0150.0
1/00.02180.0300.0

1.NEC recommends max 3% VD for branch circuits

2.NEC recommends max 5% total VD (feeder + branch)

3.Values based on K = 12.9 for copper at 75°C

NEC 210.19(A) Informational Note No. 4: Branch circuits should not exceed 3% voltage drop. The total of feeder and branch circuit drops should not exceed 5%.

Three-Phase Voltage Drop Tables

Voltage Drop — 480V 3Φ Copper (per 100 ft, per amp)

NEC 215.2(A)(4) Info Note 2
Voltage Drop per Amp per 100 ft — 480V 3Φ Copper
AWGVD/A/100ftMax Amps @3%Max Amps @5%
140.5426.544.1
120.3442.170.1
100.2266.9111.5
80.14106.4177.4
60.085169.1281.8
40.054269.0448.3
20.034427.6712.7
1/00.021680.21133.7

1.VD/A/100ft = (1.732 × K × 100) ÷ CM

2.Values based on K = 12.9 for copper at 75°C

3.3% of 480V = 14.4V; 5% of 480V = 24V

Quick Lookup: Max Distance at 3% Drop

Max One-Way Distance at 3% VD — 120V

NEC 210.19(A) Info Note 4
Max Distance (ft) at 3% Voltage Drop — 120V 1Φ Copper
AWG15A20A30A40A50A
14382919
1261463023
109772483629
8154115775846
62441831229273
4388291194146116
2617463309231185

1.D = (VD × CM) ÷ (2 × K × I) where VD = 3.6V (3% of 120V)

2.— = wire not rated for this amperage

3.Based on copper conductors, K = 12.9 at 75°C

4.For 240V, multiply distances by 2

Formula: Max distance (ft) = (3.6 × CM) ÷ (2 × 12.9 × I) = (3.6 × CM) ÷ (25.8 × I)