Conduit Fill

Maximum conductor counts for EMT, RMC, and PVC conduit with fill percentage rules.

4 reference items · 4 sections

EMT (Electrical Metallic Tubing)

Max THHN/THWN Conductors in EMT

NEC Chapter 9, Table 4 Conduit Fill Calculator
Maximum Number of THHN/THWN Conductors in EMT
AWG½"¾"1"1¼"1½"2"2½"3"4"
141222356184138
12916264561101
105101628386399154239
83691622365788137
6247121626416499
412471016253960
31246814223352
21135712182944
1112458132032
1/0011347111727
2/0011346101523
3/001123581219
4/001113471016
2500011235813
3000011135711
3500011134710
400000112469
500000111357

1.Based on NEC Chapter 9, Tables 4 & 5

2.0 = conductor too large for this conduit size

3.— = not typically needed for this wire size

RMC (Rigid Metal Conduit)

Max THHN/THWN Conductors in RMC

NEC Chapter 9, Table 4
Maximum Number of THHN/THWN Conductors in RMC
AWG½"¾"1"1¼"1½"2"2½"3"4"
141018295170116169261407
1271322385185124191298
10581324325378120187
83581318304469107
6135101322325078
41246813203048
31135712172641
21134610142235
1011347101625
1/001134691422
2/001123571118
3/001113461015
4/00011245813
2500011134711
300000112469
350000112358
400000111357
500000111246

1.Based on NEC Chapter 9, Tables 4 & 5

2.RMC has slightly smaller internal diameter than EMT

PVC Conduit (Schedule 40)

Max THHN/THWN Conductors in PVC Sch. 40

NEC Chapter 9, Table 4
Maximum Number of THHN/THWN Conductors in PVC Schedule 40
AWG½"¾"1"1¼"1½"2"2½"3"4"
141121346082135190297464
1281525446099139217339
105101628386288137214
83591621355078122
6246111526365688
412471016223554
31236813193047
21135711162540
1012358111828
1/0011347101524
2/001123681320
3/001123571117
4/00011246914

1.Schedule 40 PVC — most common for general wiring

2.Schedule 80 PVC has thicker walls (less fill area)

Conduit Fill Rules

Maximum Conduit Fill Percentages

NEC Chapter 9, Table 1
Maximum Percent Fill of Conduit/Tubing
Number of ConductorsMax % Fill
1 conductor53%
2 conductors31%
3 or more40%
These percentages apply to the total cross-sectional area of the conduit's internal diameter. Nipples (≤ 24 inches) are allowed 60% fill.