Ampacity Tables

Copper and aluminum conductor ampacity tables with derating and correction factors.

4 reference items · 3 sections

Copper Conductors

Copper Conductor Ampacity (60/75/90°C)

Allowable Ampacities — Copper Conductors
AWG/kcmil60°C (TW, UF)75°C (THW, THWN)90°C (THHN, XHHW)
14152025
12202530
10303540
8405055
6556575
4708595
385100115
295115130
1110130145
1/0125150170
2/0145175195
3/0165200225
4/0195230260
250215255290
300240285320
350260310350
400280335380
500320380430
600355420475
700385460520
750400475535
800410490555
900435520585
1000455545615

1.Based on ambient temperature of 30°C (86°F)

2.Not more than 3 current-carrying conductors in raceway/cable

3.14 AWG: max 15A overcurrent protection

4.12 AWG: max 20A overcurrent protection

5.10 AWG: max 30A overcurrent protection

For ambient temperatures other than 30°C, apply temperature correction factors. For more than 3 current-carrying conductors, apply adjustment factors.

Aluminum / Copper-Clad Aluminum

Aluminum Conductor Ampacity (60/75/90°C)

NEC 310.16
Allowable Ampacities — Aluminum Conductors
AWG/kcmil60°C (TW, UF)75°C (THW, THWN)90°C (THHN, XHHW)
12152025
10253035
8304045
6405060
4556575
3657585
27590100
185100115
1/0100120135
2/0115135150
3/0130155175
4/0150180205
250170205230
300190230255
350210250280
400225270305
500260310350
600285340385
700310375420
750320385435
800330395450
900355425480
1000375445500

1.Based on ambient temperature of 30°C (86°F)

2.Not more than 3 current-carrying conductors in raceway/cable

3.Aluminum 12 AWG: max 15A overcurrent protection

Derating & Correction Factors

Temperature Correction Factors

NEC 310.15(B)
Ambient Temperature Correction Factors
Ambient °CAmbient °F60°C75°C90°C
21-2570-771.081.051.04
26-3079-861.001.001.00
31-3588-950.910.940.96
36-4097-1040.820.880.91
41-45106-1130.710.820.87
46-50115-1220.580.750.82
51-55124-1310.410.670.76
56-60133-1400.580.71
61-65142-1490.470.65
66-70151-1580.330.58

1.Multiply the ampacity from the table by the correction factor

2.For ambient temps above 30°C, factors reduce ampacity

Example: 10 AWG THHN (90°C column = 40A) at 45°C ambient → 40 × 0.87 = 34.8A

Conduit Fill Adjustment Factors

NEC 310.15(C)(1)
Adjustment Factors for More Than 3 Current-Carrying Conductors
ConductorsAdjustment Factor
4-680%
7-970%
10-2050%
21-3045%
31-4040%
41+35%

1.Apply to ampacity from table — multiply ampacity by factor

2.Neutral conductors carrying only unbalanced current are not counted

3.Equipment grounding conductors are not counted

When both temperature correction AND conduit fill adjustment apply, multiply both factors together. Example: 10 AWG THHN at 40°C with 6 conductors → 40A × 0.91 × 0.80 = 29.1A