The Most Important Conduit Rule: Tighten Every Set Screw and Locknut
Why loose EMT set screws and locknuts are dangerous: the conduit is part of the ground-fault path, and a poor connection can leave it energised.
A Small Fitting With a Big Job
A set screw EMT connector is about as ordinary as electrical hardware gets. They come in different sizes, finishes and metal compositions, and most electricians install thousands of them without giving them a second thought. But in a recent Electricians in Action lesson, the Electrical Code Coach makes the case that tightening this fitting properly is one of the most important things you do when running conduit.
The reason comes down to one fact that newer electricians often don’t realise:
“The pipe itself is actually allowed to be used as an equipment grounding conductor.”
Once you understand that the raceway is part of the fault-clearing path, a loose set screw stops being a workmanship issue and becomes a safety issue.
What NEC 250.118 Says
The Electrical Code Coach points straight to NEC 250.118, which lists the types of equipment grounding conductors (EGCs) the code recognises:
“I highly recommend that you go read 250.118. It’s going to tell you a whole list of things that you may not have known that you can actually use as the equipment grounding conductor.”
Electrical metallic tubing is on that list. So are rigid metal conduit and intermediate metal conduit, among others. That means a properly installed metal raceway can serve as the EGC without a separate green wire being pulled.
The key words are properly installed. A wire-type EGC is one continuous conductor. A conduit-type EGC is a chain of separate pieces of pipe joined by couplings, connectors and locknuts, and the chain is only as good as its weakest joint.
Scenario One: The Conduit Is the Equipment Ground
The first example in the video is a common one. You’re in a warehouse, there’s a panel on the wall, and you need to run a receptacle downstream. You install the EMT and set screw couplings, and you decide not to pull a green wire. You pull only a hot and a neutral for a 120-volt circuit and rely on the pipe as the equipment grounding conductor.
When everything is tight
A few months later, someone plugs in a saw with a ground fault. Here is what should happen:
- Fault current flows through the ground prong of the cord into the receptacle and the box
- It travels along the EMT, through every coupling and connector, back towards the panel
- Because the path is low resistance, the current rises quickly
- The overcurrent device sees that high current and trips
As the Electrical Code Coach describes it, the fault current “trips the breaker, heads back to the source, winning on all sides.” The fault is cleared almost instantly and nobody is hurt.
When one set screw is loose
Now run the same fault with one loose set screw somewhere in the run. It doesn’t have to be completely undone. It only has to be loose enough to add resistance to the path.
“It may be tight enough to let a few amps through, but it’s not enough to raise the overcurrent enough to trip the breaker. So, we have a fault standing.”
This is the critical point. A breaker needs a high fault current to open quickly. A poor connection limits that current, so the breaker never sees a fault. The circuit stays live, and everything on the load side of the loose fitting stays energised:
- The outlet box
- The metal parts of the tool that’s plugged in
- The length of conduit downstream of the loose fitting
- Potentially the coupling itself
All of it can be sitting at 120 volts to ground, with no indication that anything is wrong. Anyone who touches that pipe while also in contact with a grounded surface, such as the building steel, could be shocked or electrocuted.
Never Grab a Separated Conduit Run
This leads to a piece of practical advice that applies on every type of job, whether you’re on a roof, in a commercial space or in a house wired in metal pipe. If you walk up to a run where a coupling has pulled apart and you can see exposed wire, the instinct is to push it back together. Don’t.
“If there’s a standing fault on this pipe right here and you walk up and grab the grounded pipe and the ungrounded pipe, you are going to be the difference in potential. From this side to that side, you’re going to be the light bulb.”
One side of the separation may still be bonded back to the panel. The other side may be energised by a fault that never cleared. Put a hand on each and your body completes the circuit.
Even if there is no standing fault, the repair itself can create one. If you pinch a conductor while pushing the pipe back into the coupling, you can energise the conduit while you’re holding it.
The rule is simple:
- De-energise the circuit first
- Verify that it’s dead
- Then make the repair
Scenario Two: You Pulled a Green Wire
It’s tempting to think that pulling a wire-type equipment grounding conductor makes the fittings less important. The Electrical Code Coach addresses that directly:
“This pipe is still metal and it still needs to be able to clear the fault in the event of there being a fault on that pipe.”
This is the bonding side of the story. Imagine a conductor gets nicked during the pull and the damaged insulation ends up resting against the inside of the conduit. The pipe is now energised and needs a path back to the source.
In a sound installation there are several ways home. The locknut bonds the connector to the enclosure, the wire-type EGC is terminated to the box and the device, and fault current will take every available path back, clearing the fault and opening the overcurrent device.
But consider what happens when things aren’t perfect:
- A locknut is loose where the connector enters the box
- A set screw is loose at one or both ends of a length of pipe
- The equipment ground was never terminated in the box, has a poor connection, or has slipped out
Combine a loose fitting with a missing or poor EGC connection and a section of conduit can be isolated from the fault path. If that section is the one the damaged conductor is touching, you are back to a standing fault on exposed metal.
A wire-type EGC is good practice, but it doesn’t remove the need to bond the raceway. The metal pipe must be able to clear a fault on its own.
What to Tighten, Every Time
The takeaway from the video is short:
“Tight all your set screws, your couplings, your connectors, and all of your lock rings. That way you’re able to clear the fault in the event of a fault.”
On every metal conduit run, check:
- Set screws on connectors where the conduit enters boxes and enclosures
- Set screws on couplings, on both sides of every joint
- Locknuts on every connector, since they bond the fitting to the box or panel
- EGC terminations, if you pulled a wire-type ground, at the box and the device
The Electrical Code Coach also mentions that the fittings may have a torque specification. Where the manufacturer provides a tightening torque, follow it. NEC 110.14(D) requires tightening torque values marked on equipment or given in the installation instructions to be achieved, so check the fitting’s packaging or listing information.
The Bottom Line
The equipment grounding path exists for one purpose: to carry enough fault current to open the overcurrent device quickly. Every loose set screw or locknut adds resistance to that path, and enough resistance means the breaker never trips.
Three things to remember:
- Metal conduit can be the equipment grounding conductor under NEC 250.118, so every joint is part of the grounding path
- Pulling a green wire doesn’t excuse loose fittings, because the raceway still has to be bonded to clear a fault on the pipe itself
- Never handle a separated conduit run while it’s energised, because you could bridge an energised section and a grounded one
It takes a few seconds per fitting, and it determines whether a fault trips a breaker or leaves a length of pipe live.
How NEC Mastery Fits Into This
Grounding and bonding is one of the most heavily tested areas on journeyman and master electrician exams, and it’s also one of the areas where candidates most often confuse terms. Knowing why the conduit has to be bonded makes Article 250 questions much easier to work through. NEC Mastery helps you build that understanding:
- 8,000+ exam-style questions include extensive coverage of Article 250, so you get repeated practice identifying equipment grounding conductors, bonding requirements and effective ground-fault current paths
- Detailed explanations referencing specific NEC sections such as 250.118 show you where each answer comes from, so you learn where grounding and bonding rules sit in the codebook
- Timed mock exams weighted to your exam type let you practise finding grounding and bonding answers under exam time limits
- Practice that pairs with your codebook reinforces the reasoning behind the rules, which is what helps on scenario-based questions like the ones in this video