HVAC Whole House Load Calculations (2026 NEC 120.6)
Learn how to handle heating and cooling loads in a 2026 NEC whole house load calculation using 120.6, with two fully worked exam-style examples.
Heating and Cooling: Do They Really Run Together?
When you’re working through a whole house load calculation, the HVAC equipment is usually one of the biggest loads on the page. So it’s worth asking a simple question before you start adding numbers: are we really going to be running the heating and the cooling at the same time?
Not usually. There are odd situations where it can happen, such as dual zone systems, but for the purposes of a dwelling load calculation the code gives us a break. Under 120.6 of the 2026 NEC, we calculate both loads and then pick the larger of the two.
This walkthrough follows lesson 4.1 from the Electrical Code Coach’s whole house load calculation series, including two worked examples you can practise against.
A Word of Warning: This Part of the Code Is Messy
Before getting into the maths, the Electrical Code Coach is refreshingly honest about this section:
“This is the only part of the program that I have to say the code is broken. In the 2026, which is the version you’re in, they did do some work to help clarify it, but there’s so many ways to interpret this, and there’s so many different nuanced situations that it’s really convoluted.”
That matters for how you study. The method below isn’t presented as the one true reading of 120.6. It’s presented as the reading your exam writers are most likely to use:
“I’m going to show you what I believe the test makers are going to be thinking when they’re creating your questions. And that’s based off of common consensus and different interpretations and the historical way that this is interpreted.”
Two takeaways from that:
- For the exam, learn the conventional method and apply it consistently
- In the field, work it out with your inspector rather than assuming this interpretation is the only acceptable one
The Method in Four Steps
Every question of this type follows the same pattern:
- Calculate the cooling load: take the compressor (the largest motor) at 125%, add the blower motor, then multiply by the voltage to get VA
- Calculate the heating load: take the heat strip rating in VA, then add the blower motor at 125% (it’s the largest motor on the heating side) converted to VA
- Check for demand factors: there are none to add here, because the 125% multiplier was already applied along the way
- Select the larger of the two: that single figure is your HVAC load for the whole house calculation
The detail people most often miss is the blower. As the instructor puts it:
“Whether we’re calculating heating or cooling, we have to be able to circulate that air.”
So the blower motor appears on both sides of the comparison.
Worked Example 1: Heating Wins
Question: How many VA would you calculate for an 18.2 amp air conditioner compressor with a 1.8 amp blower and a 10 kW heat strip, all rated 240 volts, on a dwelling unit?
Cooling load
- Largest motor is the compressor: 18.2 A × 1.25 = 22.75 A
- Add the blower: 22.75 A + 1.8 A = 24.55 A
- Convert to VA: 24.55 A × 240 V = 5,892 VA
Heating load
- Heat strip: 10 kW = 10,000 VA
- Largest motor on the heating side is the blower: 1.8 A × 1.25 = 2.25 A
- Convert to VA: 2.25 A × 240 V = 540 VA
- Total: 10,000 VA + 540 VA = 10,540 VA
Compare and select
- Cooling: 5,892 VA
- Heating: 10,540 VA
The heating load is larger, so the answer is 10,540 VA.
Why the 125% Debate Rarely Changes the Answer
The step that causes the most argument is that extra 125% on the blower in the heating calculation. Because the heating and cooling loads are being treated as separate scenarios, following the code to the letter means identifying the largest motor in each scenario, and on the heating side the only motor is the blower.
This is the part the instructor describes as getting “off in the weeds”, and he’s hoping a public input for the 2029 cycle will tidy it up. But he also makes a practical point that should take some of the stress out of it:
“That little bit of an add-on, and whether or not you add it and where you add it, of doing the 1.25, doesn’t make a difference in this overall calculation. Look how much larger the heating is.”
In Example 1, the gap between heating and cooling is more than 4,600 VA. The blower’s 25% adder is worth only 108 VA (0.45 A × 240 V). In most real-world and exam scenarios, one load is clearly bigger than the other, and where exactly the 1.25 lands won’t change which one you select. It can, however, change the final figure by a small amount, so on a multiple-choice exam, work it the conventional way and match your result to the options given.
Worked Example 2: Cooling Wins
Question: How many VA would you calculate for a 28.2 amp air conditioner compressor with a 3.2 amp blower motor and a 6 kW heat strip, all rated 240 volts, on a dwelling unit?
Cooling load
- Largest motor is the compressor: 28.2 A × 1.25 = 35.25 A
- Add the blower: 35.25 A + 3.2 A = 38.45 A
- Convert to VA: 38.45 A × 240 V = 9,228 VA
Heating load
- Heat strip: 6 kW = 6,000 VA
- Blower at 125%: 3.2 A × 1.25 = 4 A
- Convert to VA: 4 A × 240 V = 960 VA
- Total: 6,000 VA + 960 VA = 6,960 VA
Compare and select
- Cooling: 9,228 VA
- Heating: 6,960 VA
This time the cooling load is larger, so the answer is 9,228 VA.
The lesson from putting these two examples side by side is simple: never assume. A big heat strip usually dominates, but a large compressor paired with a small heat strip flips the result. Always run both calculations.
Common Mistakes to Avoid
- Adding heating and cooling together: 120.6 has you compare them and keep the larger, not sum them
- Forgetting the blower motor: it belongs in both the heating and the cooling calculation
- Applying 125% to the wrong motor: it goes on the largest motor in each scenario, which is the compressor for cooling and the blower for heating
- Forgetting to convert amps to VA: multiply by the rated voltage (240 V in both examples) before comparing
- Mixing units: a 10 kW heat strip is 10,000 VA; convert it before you add anything to it
- Hunting for an extra demand factor: once the 125% has been applied, there are no additional multipliers for this step
The Bottom Line
HVAC loads in a whole house load calculation come down to a short, repeatable routine:
- Cooling = (compressor amps × 1.25 + blower amps) × voltage
- Heating = heat strip VA + (blower amps × 1.25 × voltage)
- Select the larger and carry that figure into your whole house load calculation
Yes, 120.6 is nuanced, and yes, there’s room for interpretation. But for exam purposes, a consistent method beats a perfect philosophical understanding. Learn the pattern, practise it until it’s automatic, and save the interpretation debate for a conversation with your inspector.
And if the code ever feels like more trouble than it’s worth, the instructor’s closing words are worth holding on to:
“Although it may be complicated and nuanced, it’s worth it. It’s one of the best industries there ever was in the entire world, and you get to be a part of it.”
How NEC Mastery Fits Into This
Calculations like this one aren’t learned by watching once. They’re learned by repetition, until the steps are second nature. That’s exactly what NEC Mastery is built for.
- 8,000+ exam-style questions give you plenty of load calculation practice, so picking the largest motor, applying the 125%, and comparing heating against cooling becomes routine
- Detailed explanations referencing specific NEC articles and sections show you where each step comes from, so you can find it again in your codebook under exam pressure
- Timed mock exams weighted to your exam type train you to work multi-step calculations quickly and accurately, without burning the clock on a single question
- Practise the nuanced areas until they stop being intimidating: the more variations you see, the easier it is to recognise what the test makers are really asking
Work through the two examples above with your own calculator, then keep practising until the method feels automatic. With the HVAC load sorted, you’re one step closer to completing a full whole house load calculation.